Flameproof Conduit Outlet Box

EXP-JBR

Flameproof Ex d conduit outlet and junction boxes for Zones 1, 2, 21 and 22, in 13 shape codes with metric or NPT threads.

IECEx
Zone 1 · 2 · 21 · 22
IP66
Up to 800 V AC
13 Shape Codes
Ex db · Ex tb
Protection
Zone 1 · 2 · 21 · 22
Suitable zones
T6 / T5
Temperature Class
IP66
Ingress Protection
800V AC
Rated Voltage
-60 to +55°C
Ambient temperature

About this Product

EXP-JBR is a range of flameproof conduit outlet and junction boxes in die-cast aluminium ADC12, Ex db IIC T6/T5 Gb for gas Zones 1 and 2 and Ex tb IIIC T80 °C/T95 °C Db for dust Zones 21 and 22, sealed to IP66 and rated up to 800 V AC. Shape KB1 is certified Ex db IIB+H2: suitable for hydrogen, but not for acetylene or carbon disulphide.

Four enclosure families cover 13 shape codes, A1 to KB1, with M20, M25 or M32 × 1.5 or 1/2", 3/4" or 1" NPT threads, under certificate IECEx TPS 25.0081X. Rated current is up to 41 A depending on shape and conductor size. Fit separately certified entry devices and blanking elements, IP66 minimum, in every hole.

Conduit SystemsGeneral Wiring in Zone 1Process PlantHydrogen Areas (KB1)Lighting CircuitsZone 21/22 Dust Areas

Hazardous-Area Certification

Gas markingEx db IIC T6/T5 Gb (all shapes except KB1) · Ex db IIB+H2 T6/T5 Gb (KB1)
Dust markingEx tb IIIC T80 °C/T95 °C Db
Suitable zonesZones 1, 2 (gas) · Zones 21, 22 (dust)
CertificateIECEx TPS 25.0081X, Issue 0 · TÜV SÜD Product Service GmbH
Ambient temperatureT6 / T80 °C at -60 °C to +40 °C · T5 / T95 °C at -60 °C to +55 °C

Electrical

Rated VoltageUp to 800 V AC
Rated current (2.5 / 4 / 6 mm²)A, B shapes 24 / 32 A · C shapes 24 / 32 / 41 A · KB1 24 / 27 A
Field WiringCable rated 80 °C minimum at +55 °C

Enclosure

HousingDie-cast aluminium ADC12, housing and cover
Ingress ProtectionIP66
Cable EntriesM20 / M25 / M32 × 1.5 · 1/2" / 3/4" / 1" NPT
FastenersProperty class A2-70

Ordering & Installation

Order codeNLC EXP-JBR + shape code + thread
EntriesSeparately IECEx-certified entry devices and blanking elements, IP66 minimum
Flameproof jointsRepair only by the manufacturer or on its behalf
InstallationTo IEC 60079-14 · do not open when an explosive atmosphere is present

Project-specific selection available

Contact our engineering team to match the model to your area classification drawing and for ordering codes.

Contact Engineering
Shape CodeSize (datasheet)Max. TerminalsEntries
A1 · A2A · A2B · A3 · A4145 × 145 mm, depth 87 mm65
A5145 × 145 mm, 112 mm per drawing65
B3139 × 157.5 mm, depth 87 mm55
B3A135 × 149.5 mm, depth 87 mm55
C4A · C4B · C6 · C8155 × 155 mm, depth 98 mm128
KB1142 × 142 mm, depth 107 mm45

Dimensions in mm. Every box is assembled to order; the nameplate states the rating of the finished assembly.