Office lighting, 500 lux, UGR 19

The European standard EN 12464-1 sets the global benchmark for office lighting: 500 lux on the desk, UGR ≤ 19 (low glare), Ra ≥ 80 (decent colour), uniformity ≥ 0.6 (even spread), and 200 lux on surrounding walls. KSA's labour-comfort regulations align with these values. Get them wrong and productivity drops 20%.

Animated explainer, press play to watch the concepts now; the filmed cut publishes once production wraps.

What you'll walk away with

Four ideas to carry into the next specification conversation you have.

01

500 lux on the working plane.

Measured at 0.75 m height, on the desk, average across the area. Reception 300 lux. CAD drafting 750 lux. Accounts 500 lux.

02

UGR ≤ 19, discomfort glare limit.

Calculated in DIALux or Relux per CIE 117. Need diffused fixtures, lower luminance, and good aiming. Mandatory in EN 12464-1.

03

Ra ≥ 80, but 90+ for skin / video calls.

Standard offices Ra 80. Meeting rooms with frequent video calls or design studios use Ra 90+ for accurate skin and product colours.

04

Daylight harvesting cuts energy 30-50%.

DALI-2 or KNX sensors near windows dim luminaires when daylight is sufficient. Mostadam and LEED reward it.

Office spaces, EN 12464-1 targets

Working-plane lux, UGR, CRI, and uniformity by office function.

Space Lux / UGR / Ra Note
Reception300 / 22 / 80Welcoming, less critical
Open-plan desk500 / 19 / 80Standard task
Conference room500 / 19 / 80+ video calls Ra 90
Drawing / CAD750 / 16 / 80Highest UGR demand
Archive / filing200 / 25 / 80Storage transient
Server room200 / 25 / 80Maintenance only
Cafeteria200 / 22 / 80Social space
Corridor100 / 28 / 60Walkway

Commissioning the productive office

Five build-quality decisions that move an office from compliant to excellent.

Vertical illuminance is the new horizontal.

EN 12464-1:2021 introduced 150 lux on walls for offices. Why? Because vertical lux drives circadian (EP59), perception of brightness, and facial visibility. Designers must hit walls too.

UGR table reports, not single number.

Modern reports show UGR at every observer position, not just average. Worst-case observer at the back of the room dictates the design. NLC DIALux deliverables include this table.

Tunable white pays for itself.

6500K morning alertness + 4000K mid-day + 3000K evening reduces afternoon slump, improves sleep, and lowers staff turnover. ROI in 2-3 years from productivity alone.

Daylight harvesting needs commissioning.

Sensors must be placed where the actual daylight is, not where the BIM model said. Always commission with a real desk and a real day, sensor placement is field-tuned.

EN 12464-1:2021 is now mandatory, not optional.

The 2021 revision added wall lux, ceiling lux, modelling, and SDCM ≤ 5. Mostadam Silver/Gold projects require compliance. Don't quote the old 2011 standard.