Episode 35 ~2:10 Power Safety EN · العربية

Arc flash & PPE categories

An electrical arc at 13.8 kV releases plasma at 19,000 °C and pressure waves that can collapse lungs. IEEE 1584 calculates incident energy in cal/cm². NFPA 70E maps that to PPE category. Saudi sites that skip the calc kill people.

Animated explainer, press play to watch the concepts now; the filmed cut publishes once production wraps.

What you'll walk away with

Four ideas to carry into the next specification conversation you have.

01

Incident energy is measured in cal/cm².

The thermal energy reaching a worker's skin during an arc fault. 1.2 cal/cm² = onset of second-degree burn at 30 cm distance.

02

PPE Category 0–4 maps the energy.

Category 0 = no special PPE (≤ 1.2 cal/cm²). Category 4 = 40+ cal/cm² arc suit. Above Category 4, work is forbidden energised.

03

Approach boundaries: flash, restricted, prohibited.

Three concentric zones around the panel. Flash protection boundary = where second-degree burn risk ends. Inside it, full PPE.

04

Calculate once, label every panel.

Arc flash labels per IEEE 1584 mandatory on every switchgear panel: incident energy at working distance, boundary distance, PPE category.

PPE category × incident energy

Per NFPA 70E Table 130.7(C)(15)(c). Saudi sites adopt the same scale.

Category Min arc rating PPE required
Category 0≤ 1.2 cal/cm²Non-melting long-sleeve + safety glasses
Category 14 cal/cm²Arc-rated FR shirt + pants OR coveralls
Category 28 cal/cm²FR shirt + pants + face shield + balaclava
Category 325 cal/cm²Arc flash suit hood + jacket + bib overall
Category 440 cal/cm²Full arc flash suit + hood + gloves
> 40 cal/cm²Not allowed energisedDe-energise first, no PPE rated

Running an arc flash study

Five steps that turn an IEEE 1584 calc into a safety system.

Model the full system, not just one panel.

Arc flash energy at any point depends on the upstream fault current and protection clearing time. ETAP, EasyPower, SKM PowerTools model the entire installation. A single calc on one panel without upstream coordination is useless.

Clearing time is the multiplier.

Incident energy is roughly proportional to fault current × clearing time. A breaker clearing in 0.05 s gives 10× less energy than one clearing in 0.5 s. Faster protection at every level is the cheapest way to drop PPE categories.

IEEE 1584-2018 changed the math.

The previous 2002 method underestimated energy at 240 V. The 2018 update added box geometry, electrode orientation, and arc-current variation. Saudi consultants still using 2002 are running outdated risk numbers.

Labels are not optional.

NFPA 70E + Saudi OSHA / SBC require an arc flash label on every panel rated > 50 V where work might be done energised. Label includes incident energy at working distance, flash boundary, and PPE category. Re-issue after any system change.

Maintenance switches reduce risk during work.

Some breakers have a 'maintenance mode' (e.g. ABB Emax MMS, Schneider Energy Reduction Maintenance Setting) that drops trip delays to minimum during planned work, temporarily reducing arc energy by 60-80%. Spec these on critical sites.

Next Episode

Harmonics & THD

Watch next

Get the next episode by email

Practical lighting know-how from NLC Academy. No spam, unsubscribe anytime.

By subscribing you agree to receive NLC emails.