Episode 36 3:36 Power Quality EN · العربية

Harmonics, and where the limits apply

Non-linear loads draw current in pulses, not sinusoids, and the distortion reaches the whole supply. Under IEEE 519, harmonic limits are assessed at the point of common coupling (PCC) for the whole installation, not one nonlinear device. Which limits bind a site depends on the regulator, connection agreement, contract or project specification.

A technician in a white hard hat and hi-vis vest holds a power quality analyser beside a row of grey drive cabinets.
Animated explainer, press play to watch the concepts now; the filmed cut publishes once production wraps.

What you'll walk away with

Four ideas to carry into the next specification conversation you have.

01

The current metric is TDD, not THD.

Both use the same numerator. THD divides by the fundamental actually flowing; TDD divides by maximum demand, the base IEEE 519 uses for current. In this modelled example one harmonic shape holds at every load, so THD stays at 110% while TDD = THD × load share: 44% at 40% of maximum demand. In real installations THD changes with load, because the harmonic currents and the operating point change. High THD alone is not a limit breach. The spectrum is an NLC illustrative model, not a measurement.

02

The duty is shared at the PCC.

IEEE Std 519-2022 shares the duty at the point of common coupling: the system owner or operator for voltage distortion, the user for the harmonic current the whole installation injects. IEEE 519 limits are not meant for one piece of equipment. Equipment emission limits come from product standards such as IEC 61000-3-2 and IEC 61000-3-12, so judge the installation, not one nonlinear load.

03

The PCC is outside your building.

IEEE Std 519-2022 (clause 3) defines it as a point on the public supply where other customers are, or could be, connected: for example the high-voltage side of a dedicated service transformer, or the low-voltage side of a shared one. A distribution board inside the building is not a PCC, so a THD reading there does not answer the PCC question that IEEE 519 frames.

04

A K-rated transformer tolerates harmonics. It does not remove them.

A K-rating gives the transformer extra thermal headroom for harmonic heating. It does not reduce the harmonic current the installation injects into the network. Reducing that injection takes a different measure: a filter, an active front end or a multi-pulse rectifier. Name the fix for the problem you have: heating, or injection.

WHERE THE LIMIT SITS
Assess the installation at the PCC
Public supplyshared supplyDedicatedtransformerYour installationdrives, LEDsPCClimits are assessed herea sub-board inside the building is not a PCCjudge the installation, not one device
In IEEE 519-2022 the PCC is a point on the public supply where other customers are, or could be, connected. A distribution board inside the building is not one. IEEE 519 states that its limits are not binding in all cases. Whether they bind a site depends on the regulator, connection agreement, contract or project specification. A limit checked on one drive or one luminaire is not an IEEE 519 installation-level assessment.
ORDER, SEQUENCE, FREQUENCY
Triplens are zero-sequence: balanced phases add them in the neutral
ordersequence50 Hz60 Hz1stpos50603rdzero1501805thneg2503007thpos3504209thzero45054011thneg55066013thpos650780the highlighted orders are the triplensbalanced phases arrive together, so they add in the neutralSaudi Arabia runs at 60 Hz: the 5th is 300 Hz
On the Saudi 60 Hz grid the 5th is 300 Hz and the 7th is 420 Hz, not 250 and 350. In a balanced three-phase, four-wire system, triplens (3rd, 9th, 15th) are in phase on all three phases, so in the neutral they add instead of cancelling.
THD IS NOT TDD
In this modelled example, THD stays constant while TDD falls with load
0%20%40%60%80%100%110%100%88%80%66%60%44%40%22%20%THD stays at 110%modelled load, as a share of maximum demandTHD: over fundamentalTDD: over max demandIEEE 519 uses TDD for current limits
THD divides by the fundamental actually flowing. TDD divides by maximum demand, the base IEEE 519 uses for current. One harmonic shape at every load: THD stays at 110%, TDD = THD × load share, so 44% at 40% of maximum demand. High THD alone is not a limit breach. In real installations THD changes with load, because the harmonic currents and the operating point change.
THE NEUTRAL
Triplens and imbalance both load the neutral; THD alone does not predict it
switch-mode suppliesneutral 1.67 x phase35791113six-pulse driveneutral 0.00 x phase5711131719amber bars are triplens: 3rd, 9th, 15thmodelled spectra, balanced supply, not measured
In a balanced three-phase, four-wire system, triplens add in the neutral at three times the per-phase value. The modelled 3rd is 81% of the fundamental. Load imbalance also produces neutral current. The modelled six-pulse drive has no triplens and zero neutral current, at about a quarter of the switch-mode THD. Do not put neutral heating down to one cause without measurement or analysis.
THE WAVEFORM
The current is a narrow pulse, and its peak is the number to check
1.81crest factorfundamental onlycurrent drawn090180270360modelled, not measured: degrees of one 60 Hz cyclea sine peaks at 1.41 times its RMSthis peaks higher on the same RMS
The modelled switch-mode current is a narrow pulse, not a sine. The modelled peak is 1.81 times the RMS, against 1.41 for a sine, assuming all harmonics are zero-phase. Equipment rated on peak current, such as a UPS inverter, may see that peak.
A hand-held power quality analyser showing three-phase waveforms, held beside a switchboard with red, yellow and blue leads.

Which limit × whose duty

The SERA framework sets the Saudi voltage THD values in the table, and they are tighter than IEEE 519 at every level shown. IEEE Std 519-2022 Table 1 sets voltage limits by bus voltage at the PCC, and its limits are assessed there for the whole installation. Equipment emission limits come from product standards such as IEC 61000-3-2 and IEC 61000-3-12, so a site full of compliant products can still exceed the site limit. Use the values the connection agreement or specification adopts.

Limit Threshold Where enforced
Voltage distortion, bus at or below 1 kV8.0% THD, 5.0% individual harmonicIEEE Std 519-2022, Table 1
Voltage distortion, bus above 1 kV up to 69 kV5.0% THD, 3.0% individual harmonicIEEE Std 519-2022, Table 1
Where the limits are assessedthe PCC, for the installationIEEE Std 519-2022, clause 3 (PCC)
Is it binding?not binding in all cases; binds once a regulator, utility, connection agreement or specification adopts itIEEE Std 519-2022, clause 1
Who carries the duty at the PCCsystem owner or operator: voltage distortion; user: the harmonic current the installation injectsIEEE Std 519-2022
Equipment emission limitsset by product standards, not by IEEE 519IEC 61000-3-2 and IEC 61000-3-12
The metric for currentTDD, over maximum demand, not THD; limits set by the short-circuit ratio at the PCCIEEE Std 519-2022, clause 3 (TDD)
Harmonic frequencies5th = 300 Hz, 7th = 420 Hz on the 60 Hz Saudi gridSERA PQ framework (issue 1), sec. 6.6.1 to 6.6.2 (60 Hz); calculation
Voltage THD standard, 230 to 400 V5.0%SERA PQ framework (issue 1), Annex 1 Table 5
Voltage THD standard, 11 and 13.8 kV4.0%SERA PQ framework (issue 1), Annex 1 Table 5
Voltage THD standard, 33 to 69 kV3.0%SERA PQ framework (issue 1), Annex 1 Table 5
Where it applies and how it is measuredall connection points; IEC 61000-4-7, 10-minute intervals, at least one weekSERA PQ framework (issue 1), sec. 6.7.2 to 6.7.3
IEC/TR 61000-3-6 and IEEE 519not referenced in the SERA frameworkSERA PQ framework (issue 1)
THE SAUDI FRAME
Saudi Arabia runs at 60 Hz, with its own THD values
0%2%4%6%5.0%230 to 400 V4.0%11 and 13.8 kV3.0%33 to 69 kVstandard values at connection pointsSERA Power Quality framework, issue 1, Annex 1 Table 5
SERA Power Quality framework, issue 1, Annex 1 Table 5: voltage THD 5.0% at 230 to 400 V, 4.0% at 11 and 13.8 kV, 3.0% at 33 to 69 kV. Applied at all connection points, measured to IEC 61000-4-7 in 10-minute intervals over at least one week. The framework does not reference IEEE 519 or IEC/TR 61000-3-6.
THREE NUMBERS
THD, neutral current and crest factor each answer a different question
THDover fundamental110%SMPS28%six-pulseneutralIn over phase1.67SMPS0.00six-pulsecrestpeak over RMS1.41sine1.81SMPSmodelled spectra, balanced supply, not measured
THD is harmonics over the fundamental, the neutral ratio is In over phase current in a balanced model, and crest factor is peak over RMS. Quote the number your question needs. A THD figure alone does not answer the other two.
CRITICAL SITES
A stricter target for a critical site is set in the specification
IEEE 519Table 1by bus voltageat the PCCSERAAnnex 1 Table 5by voltage levelconnection pointscritical sitestate the targetin the specwith its metricstate a stricter target in the specification
IEEE 519-2022 Table 1 sets voltage limits by bus voltage at the PCC. A hospital, data centre or airport that needs a tighter target writes it into the specification, with the value, the measurement point and the metric. Do not assume a stricter target from the site category. Write it into the specification.
THE MISTAKE: A K-RATED TRANSFORMER
A K-rated transformer tolerates harmonics. It does not remove them
K-rated transformerchanges: heating margininside the transformerharmonics: not reducedFilter, active front endor multi-pulse rectifierchanges: what the siteinjects into the gridreduces the injectionK-rating protects the transformer, not the grid
K-rating gives the transformer extra thermal headroom for harmonic heating. It does not reduce the harmonic current the installation injects into the network. Reducing what the installation injects takes a different measure: a filter, an active front end or a multi-pulse rectifier. Name the fix for the problem you have: heating, or injection.
THE CORRECTION: MEASURE AT THE PCC
Measure at the PCC, against the right metric
UtilityTransformerMain boardSub-boardPCC: measure herenot the PCC×TDD for current, THD for voltage, at the PCCa sub-board reading answers a different question
A THD reading at a sub-board does not answer the PCC question that IEEE 519 frames. Under IEEE 519-2022, current is compared with the TDD limits at the PCC, and voltage with the THD and individual harmonic limits at the same point.

Diagnosing harmonic problems

Five common assumptions, and what the standard and the physics say.

Triplens and imbalance both load the neutral; THD alone does not predict it.

In a balanced three-phase, four-wire system, triplen harmonics (3rd, 9th, 15th) are in phase on all three phases, so they add in the neutral at three times the per-phase value. In the modelled switch-mode spectrum the 3rd is 81% of the fundamental, and in this balanced model the neutral carries 1.67 times the phase current. Load imbalance also produces neutral current. The modelled six-pulse drive has no triplens, so on a balanced supply it puts zero current in the neutral, at about a quarter of the switch-mode THD. The spectra are an NLC illustrative model, not measured, and a THD reading alone cannot size a neutral. Do not put neutral heating down to one cause without measurement or analysis.

Harmonic order sets a frequency, and in Saudi Arabia that frequency is 60 Hz.

On the 60 Hz grid the 5th harmonic is 300 Hz and the 7th is 420 Hz, not 250 and 350. Filter tuning written for 50 Hz, such as a filter tuned to the 5th at 250 Hz, does not carry over to 60 Hz without recalculation. An analyser set to the wrong fundamental labels every order wrongly.

The waveform, and why crest factor matters.

In the modelled switch-mode spectrum the current is a narrow pulse, not a sine. Its peak is 1.81 times the RMS, against 1.41 for a sine. Equipment rated on peak current, such as a UPS inverter, may see that peak rather than the RMS. The 1.81 is a model result that assumes zero-phase harmonics, so a measured spectrum may differ.

The limits bind a site only once they are adopted.

IEEE Std 519-2022 (clause 1) states that its limit values should not be considered binding in all cases. The limits bind a site once a regulator, utility, connection agreement or project specification adopts them. The SERA Power Quality framework (issue 1) sets its own voltage THD values, applied at all connection points and measured to IEC 61000-4-7, and does not reference IEEE 519 or IEC/TR 61000-3-6. Use the values the connection agreement or specification adopts.

A stricter target for a critical site belongs in the specification.

IEEE Std 519-2022 Table 1 sets voltage limits by bus voltage at the PCC: 8.0% THD and 5.0% for any single harmonic at or below 1 kV, and 5.0% THD and 3.0% single above 1 kV up to 69 kV. The SERA values in the table above are tighter at every level they cover. A hospital, data centre or airport that needs a tighter target writes it into the specification, with the value, the measurement point and the metric. Do not assume a stricter target from the site category.

THE CORRECTION: WHO CARRIES THE DUTY
Judge the installation, not one nonlinear load
PCCPCCowner or operatormeets the userinstallationlimits at PCCwhole installationone loadnot the test basisone nonlinear loadjudge the installation, not a single device
IEEE 519-2022 shares the duty at the PCC: the system owner or operator for voltage distortion, the user for the harmonic current the whole installation injects. IEEE 519 limits are not meant for one piece of equipment. Equipment emission limits come from product standards such as IEC 61000-3-2 and IEC 61000-3-12. The limits bind a site once a regulator, utility, connection agreement or project specification adopts them.
THE CLAUSE TO COPY
Write the limit in five parts, each one checkable
PointPCC on the public supplyCurrent metricTDD over maximum demandVoltage metricTHD and singles at the PCCScopewhole installation, not one loadBasis60 Hz: 5th at 300 Hz, 7th at 420 Hzcite the IEEE 519-2022 edition and the clause used
A template for one project specification: check each part against drawings or a measurement report.
CHECKLIST
Before the spec goes out
Point of common coupling named in the specTDD for current, THD for voltagelimits judged on the installation, not one devicefrequency basis 60 Hz, orders at 300 and 420 Hzedition and clause cited and checked
Every item traces to a source on the next slide.
SOURCES
Where every claim in this carousel comes from
SERA, issue 1Saudi voltage THD, 60 Hz, measurement methodIEEE Std 519-2022PCC and TDD (clause 3), voltage limits (Table 1)K-factor referencetransformer heating margin under harmonicsNLC illustrative modelspectra, THD, neutral ratio, crest factor, TDD
SERA Power Quality framework, issue 1, Annex 1 Table 5 IEEE Std 519-2022, clause 3 and Table 1 Power Monitors, Power Transformer K-Factor (whitepaper) NLC illustrative model (modelled spectra) IEC 61000-3-2 and IEC 61000-3-12, equipment emission limits Standards are cited by number, edition and table or clause. Values marked come from an NLC illustrative model, not from measurements.
Next Episode

Detuned Capacitor Banks

Watch next

Get the next episode by email

Practical lighting know-how from NLC Academy. No spam, unsubscribe anytime.

By subscribing you agree to receive NLC emails.

Sources & further reading

Which document says it, and which clause.

Forward the carousel to a colleague

A 18-slide explainer, ready to post straight to LinkedIn as an image carousel. Same content, faster reading.