Episode 39 ~2:10 Backup Power EN · العربية

UPS sizing, kW, kVA, autonomy

A UPS spec sheet headlines kVA. Reality is kW × power factor. Battery autonomy is calculated at end-of-life capacity (80% nominal), not new. And the topology you pick decides whether your data centre survives a 50 ms grid sag or only a full blackout.

Animated explainer, press play to watch the concepts now; the filmed cut publishes once production wraps.

What you'll walk away with

Four ideas to carry into the next specification conversation you have.

01

kW ≠ kVA. Always.

UPS rated 100 kVA at 0.9 PF = 90 kW real. A 100 kVA UPS feeding a 0.8 PF load delivers only 80 kW. Catch the spec sheet trap.

02

Online double-conversion is the data-centre standard.

Continuously regenerates output sine wave. < 4 ms transfer time effectively zero. Survives any input event. Most expensive, most protection.

03

Line-interactive is OK for offices.

Cheaper, lower efficiency, ~ 4-10 ms transfer time. Acceptable for IT in offices but not for medical or industrial.

04

Battery autonomy at end-of-life capacity.

VRLA batteries at year 5 deliver 80% of nominal Ah. A 15 min design becomes 12 min in service. Size for end-of-life or replace earlier.

UPS topology × response × use case

Per IEC 62040-3 classification.

Topology Transfer time / class Best for
Standby (offline)8-12 ms · Class 3Home PCs, small office
Line-interactive4-10 ms · Class 3Mid-office IT, retail POS
Online double-conversion0 ms (continuous) · Class 1Data centres, hospitals, industry
Delta conversion (online)0 ms · Class 1Premium high-efficiency online
Modular / scalable0 ms · Class 1Growing data centres, hot-swap
Ferroresonant0 ms · Class 1Heavy industrial, harmonic-rich

Sizing the right UPS

Five steps that turn a kVA number into a working system.

Compute the load in kW, not kVA.

Sum every device's real power consumption. Servers, routers, AC for the server room, emergency lights, security panels. Apply diversity factor (typically 0.8-0.9) for IT loads where not every device runs at peak.

Pick the UPS topology by your tolerance.

Hospital ICU = online, 0 ms transfer. Office IT = line-interactive, < 10 ms acceptable. Data centre = online, often with delta conversion for 97% efficiency to cut Saudi cooling costs.

Size kVA from kW × PF.

If your loads draw at PF = 0.95 (modern IT with active PFC), kVA ≈ kW / 0.95. UPS catalogue rates at output PF 0.9-1.0 depending on model, read the fine print.

Design battery for end-of-life autonomy.

Target autonomy at year 5 capacity (80% of new). 15-minute design new = 12 min EOL. Or oversize batteries 25% so 12-min EOL still meets the 15-min target.

Plan paralleling for N+1.

Two 100 kVA UPS in parallel = redundancy. If one fails, the other carries the load alone. Common in data centres > 50 kVA. Adds capital cost but eliminates single-point-of-failure.

Next Episode

ATS, Automatic Transfer Switch

Watch next

Get the next episode by email

Practical lighting know-how from NLC Academy. No spam, unsubscribe anytime.

By subscribing you agree to receive NLC emails.